Comprehensive SNMP monitoring plugin for Vertiv/Liebert UPS devices in Checkmk 2.3.x.
- 📊 52+ SNMP OIDs monitored across battery, power, and environmental metrics
- 🔌 Dual Protocol Support: RFC1628 standard UPS MIB and Liebert enterprise MIBs
- ⚡ Smart Fallback: Automatically falls back from Liebert OIDs to RFC1628 when needed
- 🌿 ECO Mode Detection: Recognizes and properly reports ECO/bypass mode as normal operation
- 📈 Rich Visualization: Comprehensive graphs and perfometers
- ⚙️ Easy Configuration: Web UI rulesets for threshold customization
- 🚀 Out-of-the-Box: Works immediately with sensible defaults
- 🌍 Multi-Voltage Support: Handles both 120V (US) and 230V (EU) systems
- Download the latest MKP package from Releases
- In Checkmk: Setup → Extension packages
- Click Upload package and select the
.mkpfile - Click Install
Test SNMP connectivity:
snmpwalk -v2c -c public your-ups-hostname .1.3.6.1.4.1.476Tested: Vertiv GXT5-1500IRT2UXL
Compatible with any Vertiv/Liebert UPS supporting:
- Liebert-GP MIB (OID: 1.3.6.1.4.1.476.1.42)
- RFC1628 UPS MIB (OID: 1.3.6.1.2.1.33)
Including: GXT5 series, Liebert GXT series, Liebert PSI series, and other Liebert-GP compatible devices.
- Charge percentage, temperature, runtime, voltage, current
- Last battery replacement date
- Alarms: battery low, over-temperature, discharging, replace battery
- Defaults: Charge WARN 20%/CRIT 10%, Temp WARN 30°C/CRIT 35°C, Runtime WARN 10min/CRIT 5min
- System status, ECO mode, output load, voltage, current, power, frequency
- Input voltage/current/frequency/power factor, voltage statistics (min/max)
- Alarms: input problem, overload, bypass unavailable, output off, inverter failure
- Defaults: Load WARN 80%/CRIT 90%, Frequency WARN ±2Hz/CRIT ±3Hz (50Hz nominal)
- Voltage: Disabled by default (configure per region)
- Ambient/inlet air temperature
- Defaults: WARN 35°C, CRIT 40°C
230V Systems (Europe/Asia):
- Upper: 253V (warn), 265V (crit)
- Lower: 207V (warn), 195V (crit)
120V Systems (North America):
- Upper: 132V (warn), 138V (crit)
- Lower: 108V (warn), 102V (crit)
50Hz Systems: Upper 52Hz/53Hz, Lower 48Hz/47Hz 60Hz Systems: Upper 62Hz/63Hz, Lower 58Hz/57Hz
Configure via: Setup → Services → Service monitoring rules → Search "Vertiv UPS"
Services not appearing?
- Test:
snmpwalk -v2c -c public UPS_IP .1.3.6.1.4.1.476 - Check Checkmk SNMP settings
- Run service discovery: Setup → Hosts → Services → Fix all
Wrong values (÷10)? → Update to v0.0.4+
System status "unknown"? → Update to v0.0.7+ (supports string status values)
Voltage alarms (230V)? → Update to v0.0.8+ (voltage thresholds disabled by default)
Metadata-Driven OID Management: All OIDs in structured table with Liebert primary + RFC1628 fallback Smart Unit Handling: Liebert OIDs return decimals, RFC1628 returns deci-units DRY Code: Helper functions eliminate repetition Declarative Alarms: Simple declarative alarm lists
local/lib/python3/cmk_addons/plugins/oposs_vertiv_ups/
├── agent_based/ # SNMP section + check plugins
├── graphing/ # Metrics, graphs, perfometers
└── rulesets/ # Web UI configuration
Contributions welcome via GitHub Issues:
- Bug reports
- Feature requests
- Pull requests
- Documentation improvements
- Device compatibility reports