homeassistant-atrea-rd5-modbus

Atrea RD5 Modbus — Home Assistant Integration

CI License: Apache 2.0

Monitor and control your Atrea RD5 ventilation unit from Home Assistant using Modbus TCP.

Features

  • 🌡️ 5 temperature sensors: outdoor air (T-ODA), supply air (T-SUP), extract air (T-ETA), exhaust air (T-EHA), indoor air (T-IDA)
  • 🔄 Ventilation mode: tracks current mode (Off / Automatic / Ventilation / Circulation / Night cooling / ...)
  • 💨 Ventilation power: current requested fan power (0–100%)
  • 🌐 BMS temperature source selects: choose between internal sensor or BMS-supplied value for T-ODA and T-IDA
  • 📡 BMS setpoint write: push outdoor / indoor temperature values from HA automations to the HVAC
  • 🍂 Heating season control: view the active season (Heating / Non-heating), configure the switching mode (TS / NTS / T-TODA / T-TODA+), and set the temperature threshold
  • Efficient batch Modbus reads — consecutive registers are merged into a single Modbus request per poll cycle
  • Zero-YAML setup via Home Assistant UI config flow
  • Configurable poll interval (5–300 s) editable post-setup without re-adding the integration

Requirements

  • Home Assistant 2024.1.0 or newer
  • Atrea RD5 unit with Modbus TCP enabled and accessible on the network (default port: 502)
  • Python package pymodbus >= 3.10.0 (installed automatically by HA)

Installation

Manual

  1. Copy the custom_components/atrea_rd5_modbus/ folder into your Home Assistant config directory:
    <config>/custom_components/atrea_rd5_modbus/
    
  2. Restart Home Assistant.
  3. Go to Settings → Devices & Services → Add Integration.
  4. Search for Atrea RD5 Modbus and follow the setup wizard.

HACS

  1. In HACS, go to Integrations → ⋮ → Custom repositories.
  2. Add https://github.com/thozza/homeassistant-atrea-rd5-modbus as type Integration.
  3. Click Download on the Atrea RD5 Modbus card.
  4. Restart Home Assistant.
  5. Go to Settings → Devices & Services → Add Integration and search for Atrea RD5 Modbus.

Configuration

The integration is configured entirely through the UI. During setup you will be asked for:

Field Default Description
Host IP address of the Atrea RD5 device
Port 502 Modbus TCP port
Unit ID 1 Modbus unit ID
Scan interval 30 Poll frequency in seconds

The connection is validated before the entry is saved — if the device is unreachable an error is shown in the form.

Entities

Entity Unit Description
T-ODA Outdoor Air °C Outdoor air temperature (sensor T-ODA)
T-SUP Supply Air °C Supply air temperature after heat recovery (sensor T-SUP)
T-ETA Extract Air °C Room exhaust air entering the unit (sensor T-ETA)
T-EHA Exhaust Air °C Air leaving the unit to the outside (sensor T-EHA)
T-IDA Indoor Air °C Indoor/room air temperature (sensor T-IDA)
Ventilation Power % Current requested ventilation fan power (0–100%)
Ventilation Mode Current operation mode (Off, Automatic, Ventilation, Circulation, ...)
T-ODA Source Select: choose outdoor temp source (Internal / BMS)
T-IDA Source Select: choose indoor temp source (CP / T-ETA / TRKn / BMS)
BMS T-ODA Setpoint °C BMS-supplied outdoor temp (write-only, −50–130 °C)
BMS T-IDA Setpoint °C BMS-supplied indoor temp (write-only, −50–130 °C)
Heating Season Current season state (Heating / Non-heating) — diagnostic
Season Switch Mode Select: season switching logic (TS / NTS / T-TODA / T-TODA+)
Season Temperature Threshold °C Outdoor temp threshold for automatic season switching (0–30 °C)

BMS Setpoints (T-ODA / T-IDA from external sensors)

The Atrea RD5 can use temperatures supplied by Home Assistant in place of its own outdoor (T-ODA) or indoor (T-IDA) sensors. This integration exposes the relevant device registers as four entities:

Entity Type Purpose
select.atrea_rd5_t_oda_source select Choose internal sensor or BMS-supplied T-ODA
select.atrea_rd5_t_ida_source select Choose CP / T-ETA / TRKn / BMS for T-IDA
number.atrea_rd5_bms_t_oda_setpoint number T-ODA value pushed to the HVAC
number.atrea_rd5_bms_t_ida_setpoint number T-IDA value pushed to the HVAC

90-second watchdog

The HVAC declares a temperature-sensor fault if a BMS-sourced value is not refreshed within 90 seconds. The integration writes to the device every time the number entity is set, but it does not run an internal periodic push — that's left to your automation. Keep your update cadence comfortably below 90 s (we recommend ≤60 s).

After a Home Assistant restart, each BMS setpoint number entity restores its last known value and immediately writes it back to the HVAC, so the watchdog window starts fresh before your automation's next trigger.

Example automation

automation:
  - alias: "Atrea: push outdoor temperature from weather sensor"
    trigger:
      - platform: time_pattern
        seconds: "/30"
    action:
      - service: number.set_value
        target:
          entity_id: number.atrea_rd5_bms_t_oda_setpoint
        data:
          value: "{{ states('sensor.outdoor_temperature') | float }}"

Pair this with select.atrea_rd5_t_oda_source set to BMS so the HVAC actually consumes the supplied value.

Heating Season

The Atrea RD5 can switch between heating season (TS) and non-heating season (NTS) automatically or on demand. This integration exposes three entities for this feature:

Entity Type Purpose
sensor.atrea_rd5_heating_season sensor Read-only diagnostic: current season (Heating / Non-heating)
select.atrea_rd5_season_switch_mode select Configure the switching mode: TS / NTS / T-TODA / T-TODA+
number.atrea_rd5_season_temperature_threshold number Outdoor temp threshold used by the T-TODA / T-TODA+ modes (0–30 °C)

Switching modes:

Mode Behaviour
TS Force heating season
NTS Force non-heating season
T-TODA Auto: switch to NTS when T-ODA ≥ threshold
T-TODA+ Auto with hysteresis: switch to NTS when T-ODA ≥ threshold, back to TS when T-ODA falls below it

Polling interval

The polling interval (default 30 s) is editable post-setup via Configure on the integration tile in Settings → Devices & Services. Allowed range: 5–300 s.

Architecture

The integration uses a single DataUpdateCoordinator (AtreaCoordinator) that owns a persistent AsyncModbusTcpClient TCP connection. On each poll cycle, registers are read in contiguous batches — consecutive same-type addresses are merged into a single Modbus request automatically. This minimises network round-trips and scales well as more sensors are added.

custom_components/atrea_rd5_modbus/
├── __init__.py       # Integration setup, coordinator + client lifecycle
├── coordinator.py    # DataUpdateCoordinator, batched Modbus reads
├── const.py          # Register map, signed10() conversion, batch grouping
├── sensor.py         # 8 read-only sensor entities (temperatures, power, mode, season)
├── select.py         # 3 select entities (T-ODA / T-IDA source, season switch mode)
├── number.py         # 3 number entities (BMS setpoints, season temp threshold)
└── config_flow.py    # UI config flow with live connection validation

To add a new sensor in the future: add one entry to REGISTER_MAP in const.py and one entry to SENSOR_DESCRIPTIONS in sensor.py. Batch grouping is recomputed automatically.

Troubleshooting

Enable debug logging in configuration.yaml:

logger:
  default: warning
  logs:
    custom_components.atrea_rd5_modbus: debug

Common issues:

  • Cannot connect — verify the device IP, port (default 502), and that Modbus TCP is enabled on the unit
  • Entities unavailable — check HA logs for Modbus errors; ensure the unit ID is correct (usually 1)
  • Stale/missing values — increase the scan interval if the device reports protocol errors on rapid polling

Disclaimer

This is an unofficial community integration. It is not sponsored by, affiliated with, or endorsed by ATREA s.r.o. in any way. Use it at your own risk.

License

Apache 2.0 — see LICENSE.